The Fireye Flame Amplifier Modules are used in conjunction with the
appropriate flame scanner to provide flame scanning capability in the
FLAME-MONITOR system. Fireye offers ultraviolet amplifiers (EUV1),
self-check ultraviolet amplifiers (EUVS4), flame rectification
amplifiers for use with flame rods and photocells (ERT1), and
auto-check infrared amplifiers: E1R1 (standard model), E1R2 (high
sensitivity - consult factory before use), and E1R3 (for solid fuels).
Self-checking ultra-violet scanners and amplifiers should be used
in applications where burner firing operation is continuous or where
the burner is on for long periods of time (e.g. 24 hours) without
cycling.
The flame amplifier must be used with the appropriate flame
scanners as shown below. When replacing any flame scanner or amplifier,
the burner should be cycled on and off several times to ensure proper
operation.
|
|
Last Updated ( Sunday, 16 October 2005 )
|