Honeywell Flame Amplifier |
|
|
|
|
Solid state plug-in amplifiers
that respond to flame detector inputs to indicate the presence of flame
when used with 7800 SERIES relay modules.
• Flame failure response time of 2.0 or 3.0 seconds. • Flame signal strength ranges from 0.0 to 5.0 Vdc. • Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation. • Flame signal test jacks to measure amplifier flame signal voltage. • Color-coded
labels identify flame detection type: Blue pulsed rectification.
Dynamic Self-Check Amplifier test the detectors and all electronic
components in the flame detection system; 7800 SERIES relay module
locks out on safety shutdown with flame detection system failure. • Compatible with existing Honeywell flame detectors (order separately).
|